SPECIFICATIONS

Electrical:
Input Voltage ............................120 or  240v AC 
Trf. Secondary Voltage ...............15v
Loop Resistance  .......................230 ohms
Output Contacts ........................3 sets of C/O contacts
O/P Contact Rating....................240v 5A 650VA Max.
Trip Lamp ................................Yes
Reset Lamp ...............................Yes
Lamp Test Facility .....................Yes
Stop Switch................................Yes

Mechanical:
Height ......................................300mm. max.
Width ......................................300mm
Depth .......................................120mm
Weight .................................... 9kg


The Industrial Conveyor Control Unit is designed to work with a variety of lockout pullkeys using a simple two wire "loop"circuit.

A remote termination device is installed at the end of the external loop circuit comprising of the pullkeys and interconnection cables. If the loop circuit is interrupted by the operation of a pullkey or a cable fault, the relay control unit causes the controlled conveyor to stop.

Designed to operate on single phase   supplies of either 120v or 240v; the unit is provided with a step-down transformer which   produces 15vac. to feed the control relays and the pullkey circuitry.

The unit is fitted with mains fuses, mains transformer and two relays. In addition, the front cover is fitted with a stop switch, a reset switch, a a lamp test switch and two indicator lamps. Three output contacts are provided for use with external control circuits.

One indicator lamps glows to indicate a trip caused by operating a pull-key or due to a   cable fault. The second lamp is housed in the actuator of the Reset Switch and glows to indicate the unit is healthy and that the control relays may be reset to start the controlled conveyor.

FEATURES

-    Water and dust resistant to IP65

-    Cable connections via terminal strip

-    Incorporates Stop switch, Reset Switch, Lamp
    Test Switch and Two Indicator Lights

-    3 sets of heavy duty output changeover
      contacts rated 240v 5A

-    Compact weatherproof enclosure

-    Low voltage output to lockout keys -15vac.

-    Works up to 4km with standard pullcable -
     (maximum loop resistance up to 230ohms)

-    Fail-Safe in operation - uses remote
      termination unit to monitor lockout lines for
     lockout or cable fault

-    Simple two wire external circuit through
      lockout keys